Fire protection

The effect of floor drains on the fire protection of joists must be considered during installation.  

For concrete floors, the concrete cover layer under the floor drain should be about 70 mm to ensure fire EI 60 without further fire tests or thermal conductivity calculations. This can be achieved with a 220 mm concrete floor and 24 mm floating filler, or 240 mm concrete. 

Contact us for solutions and further information. 

Did this article help you?

0
0

Contact Us

Porträtt av Henrik Hagman på Enduce

Henrik Hagman

Technology and product manager 
henrik.hagman@enduce.se
070-947 57 43

More from the knowledge bank

The installation of the Enduce energy recovery floor drain leads to a significant reduction of energy consumption during the operational phase (EPD module B1).
Calcareous water does not have a problematic impact on the floor drain either on the gray water side (used shower water) or the tap water side. 
A hot water-based cleaning system heats, melts and flushes greasy deposits out of the heat recovery system's heat exchanger.

Learn more at our webinars

Welcome to our open webinars where we present Enduce E1. During 45 minutes you will get a deeper understanding of our solution and the opportunity to ask questions. 

New! We now offer webinars with different focus areas. See which ones interest you most via the link below. A warm welcome to you!